• fullsquare@awful.systems
    link
    fedilink
    arrow-up
    15
    ·
    5 days ago

    this shorts live and neutral, ground pin is not even present (different shape) otoh if you need help wiring a plug, you probably shouldn’t

      • Darkassassin07@lemmy.ca
        link
        fedilink
        English
        arrow-up
        6
        ·
        5 days ago

        This is a plug. The big pins are live + neutral, which are shorted together and connected to the wire labeled ground (which heads to the exposed metal of whatever appliance is on the end of this cable).

      • onslaught545@lemmy.zip
        link
        fedilink
        arrow-up
        2
        arrow-down
        8
        ·
        5 days ago

        Yeah, this circuit would do a whole lot of nothing since the ground is the only wire entering the circuit.

        • Ilovethebomb@sh.itjust.works
          link
          fedilink
          arrow-up
          5
          arrow-down
          1
          ·
          5 days ago

          It would put phase directly on the metal casing of the appliance, if the circuit protection didn’t work.

          Please avoid the temptation to comment on something you know nothing about, this is actually a serious safety concern if someone followed this diagram.

          • fullsquare@awful.systems
            link
            fedilink
            arrow-up
            2
            ·
            5 days ago

            Even worse. Orientation of pins like this is used in 240V circuit which means it has two antiphase live wires. This means that after shorting them, if one trips but not the other (if these two have independent breakers - idk if code requires otherwise) 120V is sent to device ground, and this one can be cut off by GFCI if used, but i hear it’s uncommon

            If it was normal 120V circuit, breaker would cut off live and left neutral connected to device ground, which still can be some 20V depending on conditions