I’m in a rental right now with a useless landlord, so I’m trying to fix the problem myself (or at least find the cause). My home’s central air AC unit is working, but doesn’t seem to be working well. There is cool air coming from the vents, but its less than I would expect, and when its 80f/27c outside, its rarely more than a single degree cooler. I’m looking for ideas to track down the problem. In particular, between the landlord’s neglect and the last tenant’s seemingly willful destruction I expect it’ll be something maintenance related.
So far I have checked:
-
The unit size relative to the property (its about 2.5 tons for a 2,500 ft² property) which the internet seemed to say was fine. That said, its a bungalow with no attic and high-cielings, so Im not sure if that could have enough effect to account for this.
-
Intakes and outlets inside the out aren’t blocked by furnature (although what I can see looking into them looks pretty dirty)
-
I tried removing the furnace filter (which, from my understanding, is also used by the AC inside the house) temporarily, although didn’t notice a significant difference.
-
I checked the cooling fins on the unit outside the house for obstructions, but there was little more than a bit of webs
I’m not an expert on these things at all, but is there anything else I can check or try?
Edit: unfortunately there is some condensation and frost on the coil box, so sounds like its a leak. Guess I’m looking at a fight with my landlord.
Is the coil outside unusually hot or is the fan outside not running well? It should be moving a lot of air, not like a jet but not like a warm fart either. If that’s the only problem then you’re in luck.
You said there’s cool air from the vents but less than you expect… less cool or less air? If the blower motor isn’t working right that’s a fix you can do, you’d just need a new one of the same motor that is in there now. Then it’s just a few bolts and screws, maybe a few wire nuts.
Is there icing up anywhere? Particularly at the coil inside the furnace. You may need to turn off the power and open an upper panel to get access to see. If that’s happening then the other guy is right and you’re low on refrigerant. A combustible gas tester is not super pricy but even if you find the leak you won’t be able to fix it yourself.
Good luck.